Every time the thermostat calls for heat, a gas furnace's control board runs the same safety checklist in the same order, and it won't move to the next step until the current one is proven. Where the sequence stops tells us which part failed. Below is how we use that to diagnose a furnace, along with the safety checks we run on every gas repair.
The startup sequence, and what you'll notice when it stops
On a typical modern furnace with a hot-surface igniter, a normal start takes about a minute from the thermostat click to warm air at the vents. When a step fails, most boards retry, usually three times, then lock out, often for around an hour. So a furnace can seem to fix itself overnight and quit again by morning.
| Step | What should happen | If it stops here, you'll notice |
|---|---|---|
| 1. Thermostat call | A 24-volt signal reaches the control board | Nothing at all: no hum, no fan |
| 2. Inducer motor | A small fan starts pulling air through the heat exchanger and out the vent | Silence after the click, or a grinding or squealing motor |
| 3. Pressure switch | Closes once the inducer proves the vent is drawing | The inducer runs and runs; nothing else happens |
| 4. Igniter | Glows bright orange (older furnaces spark or use a pilot) | No glow through the burner window |
| 5. Gas valve | Opens, and the burners light one after another | The igniter glows, then goes dark with no flame |
| 6. Flame sensor | Proves the flame within seconds | Burners light, then shut off a few seconds later |
| 7. Blower | Starts after a short delay and pushes warm air through the ducts | Burners running, but no air from the vents |
| 8. Limit switch | Watches heat exchanger temperature for the whole cycle | Burners cut out after a few minutes while the fan keeps blowing |
Read the blink code before you open anything
Most furnaces with an electronic control board have an LED that flashes a fault code, visible through a small sight glass in the lower door. Count the flashes between pauses, watch the pattern repeat twice, and take a short phone video. The legend that translates it is usually on a sticker inside the door.
Read it before you pull the door or flip the power switch: removing the blower door cuts power through a safety switch, and on many boards that clears the code. Codes also differ by brand, so generic charts online can mislead.
Safe checks first: thermostat on Heat and a few degrees above room temperature, fresh batteries, the furnace breaker reset once (if it trips again, leave it off), the power switch near the furnace on, a clean filter, and the lower door seated firmly.
What fails at each step, and how we prove it
A blink code tells us which step stopped. Finding out why takes testing, and we do that before we replace anything.
Hums but never lights: inducer, pressure switch and vent
When the inducer runs but nothing follows, the pressure switch isn't sensing enough draft. Sometimes the switch has failed. More often it's doing its job, and worn inducer bearings, a cracked or water-filled sensing hose, a nest in the vent cap or a clogged condensate trap is behind the code. We measure the draft with a manometer and compare it to the rating stamped on the switch. We never jumper a pressure switch to get the heat back on.
Glows or clicks, but no flame: igniter and gas valve
Hot-surface igniters are brittle. A hairline crack is enough to stop one glowing, and a weak one may not get hot enough to light the gas. If the igniter checks out, we confirm the gas is on at the valve and meter (or the propane tank isn't empty) and that the board is sending 24 volts to the valve. Then we measure gas pressure against the rating plate; on natural gas, burner pressure is commonly set around 3.5 inches of water column, and propane runs much higher.
Lights, then quits in seconds: the flame sensor
This is the most common no-heat call of the season. The flame sensor is a thin rod that proves flame by passing a tiny current, measured in microamps, through it. As a coating builds up, the signal drops until the board shuts off the gas. We clean it, measure the signal, and check the ground and burner alignment. A sensor that needs cleaning every winter has a cause, and we look for it.
Runs, but the house stays cold: blower and limit switch
If the blower doesn't carry the heat away, the limit switch shuts the burners off to protect the heat exchanger, then resets and does it again. Sometimes the blower is the problem: a failed capacitor, worn bearings, a bad variable-speed module. Just as often the airflow is restricted by a clogged filter, closed registers, a dirty AC coil on top of the furnace or crushed attic ducts (see ductwork repair and testing). We measure the temperature rise and compare it to the range on the rating plate. Swapping the limit switch won't help while the airflow problem is still there.
Next to the burners sits a flame rollout switch. It trips when flames curl out of the combustion chamber instead of being drawn in, and most need a manual reset. A tripped rollout switch points to a blocked flue or a damaged heat exchanger. Don't keep resetting it.
Attic furnaces lying on their side
Many North Texas homes sit on slabs, so the furnace often goes in the attic, installed horizontally with the AC coil on one end. That changes how problems show up.
- Nobody looks at it. Rust streaks, a sagging vent connector or scorch marks near the burners can go unnoticed for years.
- The drain pan can shut everything off. The pan under the unit usually has a float switch that cuts power when water collects, so a blank thermostat in January may just mean a full pan.
- The vent crosses the coldest, dustiest space in the house. A metal vent pipe that has slipped apart at a joint can spill exhaust into the attic, so it's worth checking whenever someone is up there.
Water problems in 90%+ furnaces
High-efficiency furnaces pull so much heat from the exhaust that water condenses out of it, so they drain all winter the way your AC does all summer. The water is mildly acidic and runs through plastic: an internal trap, hoses, a drain line and often a small pump.
When any of that clogs, water backs into the pressure switch hose and the furnace locks out with what looks like a pressure switch fault. Cleaning the trap and re-pitching the hoses fixes it; the switch was fine all along. Stuck pump floats, flat drain lines and attic lines that freeze in a hard cold snap cause the same shutdown. Outside, leaves, wasp nests or ice can block the PVC pipes. Trap cleaning is part of a fall heating tune-up.
Cracked heat exchangers and carbon monoxide: how we check
The heat exchanger is the metal wall between the flame and the air you breathe. Age, corrosion and years of overheating from poor airflow can crack it. Much of it is hidden inside the cabinet, so anyone who calls a crack from a quick glance is guessing. We build the case from several tests:
- CO readings in the living space when we arrive, near the furnace, and at supply registers once it's running.
- Combustion analysis: a flue probe measures oxygen and CO. A reading that jumps when the blower starts suggests house air is reaching the combustion side.
- Flame behavior: burners that lift, wave or roll when the blower comes on.
- A look inside with a light and inspection camera, plus clues like soot, rust scale and a tripped rollout switch.
A crack doesn't always push CO into the house, because the inducer keeps the combustion side under suction. Cracks do grow, though. They disturb the flame and can let exhaust into the airstream. When we confirm one, we shut the furnace off and show you the photos and readings. If the evidence is borderline, we'll tell you that, and you're welcome to get a second opinion. Heat exchangers often carry a longer manufacturer warranty than other parts, so we look up the model and serial number before you price a furnace replacement.
If you smell gas or a CO alarm goes off
Gas carries an added rotten-egg odor so you can smell a leak. If you do, get everyone out and don't operate switches or phones on the way. From outside, call 911 and Atmos Energy's 24-hour emergency line at 866-322-8667 (Atmos supplies natural gas in Terrell); on propane, call your supplier. Leaks in the house piping are a licensed plumber's job; once responders clear the home, we handle the furnace side.
A sounding CO alarm gets the same response: everyone out, pets included, then call 911. Carbon monoxide has no smell, and headaches or nausea that ease once you leave the house are a classic sign. Keep the furnace off until it has been checked. If it happens during a freeze, our emergency heating repair page covers staying warm safely while you wait.